PLASdek® Counter-Flow Cooling Tower Fills

Different types for all requirements – available in PVC and PP

From small cooling towers to large cell and natural draught cooling towers: Our PLASdek® packings fulfill all requirements. Different types of film fills with large specific surface are highly suited for clean and medium water qualities, whereas for special operation conditions and for strongly polluted water grid structures are the best choice. Ask our experts. They have long time experience and will be grateful to help you choose the right fill for your application.

Features

  • Excellent heat and mass transfer

    • Due to high mixing turbulence by cross-fluted structure
  • High resistance to erosion

    • Provided by double folded PVC edges or reinforced PP edges
  • Self supporting structure

    • High bearing capacity achieved by large number of connecting points and variable sheet thicknesses
  • Flexibility in material and dimensions

    • Adaptation to plant requirements according to customer request
  • Long service life

    • Due to chemical, bacterial and UV resistance of PP and PVC

Overview: PLASdek® Cooling Fills made of Polypropylene

Highly efficient with large specific surface, suited for clean cooling water

KPP 312 KZP 312 KFP 319
Contact surface [m²/m³] 232 240 150
Corrugation height [mm] 12 12 19
Channels Cross-fluted Cross-fluted Cross-fluted

Low fouling fills, for slightly and medium polluted water

KVP 319 KGP 320 KBP 320 KVP 323 KFP 327
Contact surface [m²/m³] 144 142 142 125 125
Corrugation height [mm] 19 20 20 23 27
Channels Vertical flow Vertical flow / off set Vertical flow / off set Vertical flow Cross-fluted

Easy to clean, for special operation conditions, for strongly polluted water

NET25 150 FC20.30 KFP 638 FC70.34
Contact surface [m²/m³] up to 130 110 70 94
Corrugation height [mm] 20 30 38 34
Channels Grid / diagonal Cross-fluted Cross-fluted Grid / horizontal
2H PLASdek® Counter-Flow Cooling Tower Fills
2H PLASdek® Counter-Flow Cooling Tower Fills
2H PLASdek® Counter-Flow Cooling Tower Fills
2H PLASdek® Counter-Flow Cooling Tower Fills

OVERVIEW: PLASDEK® COOLING FILLS MADE OF PVC

Highly efficient with large specific surface, suited for clean cooling water

KZC 312 KPC 312 KFC 319
Contact surface [m²/m³] 240 232 150
Corrugation height [mm] 12 12 19
Channels Cross-fluted Cross-fluted Cross-fluted

Low fouling fills, for slightly and medium polluted water

KVC 319 KGC 320 KBC 320 KFC 327
Contact surface [m²/m³] 144 142 142 125
Corrugation height [mm] 19 20 20 27
Channels Vertical flow Vertical flow Vertical flow / off set Cross-fluted

General Technical Data of 2H PLASdek® Fills

PP PVC
Void ratio [%] > 97
Length max [mm] 2400
Width max [mm] 600
Standard height [mm] 300 or 600
Continuous operation temperature [°C] 80 55
Max. operation temperature (short term) [°C] 90 60
Maximum application temperature:

The operational temperature should be measured at the inlet pipe of the system and should not exceed the maximum temperature stated above.

High temperature applications:

Fill media in high temperature in PP (up to 100°C) available on request.

Flammability:

Products in flame retardant version according to American (ASTM E84, UL 94) and European standards (DIN 4102, NF P 92-501) are available on request. National regulations on fire protection should be taken into consideration before choosing a product.

DIFFERENT TYPES OF FILLS

2H PLASdek® Counter-Flow Cooling Tower Fills KPP 312 KPC 312 KZP 312 KZC 312 KFP 319 KFC 319 KFP 327 KFC 327 KFP 638 KFC 638
Contact surface [m²/m³] 232 240 150 125 70
Void ratio [%] > 97 > 97 > 97 > 97 > 97
Corrugation height 12 12 19 27 38
Note KFP/KGP/KVP/KBP = Fills in PP
KFC/KGC/KVC/KBC = Fills in PVC
2H PLASdek® Counter-Flow Cooling Tower Fills KVP 319 KVC 319 KGP 320 KGC 320 KBP 320 KBC 320 KVP 323 KVC 323
Kontaktoberfläche [m²/m³] 144 142 142 125
Freies Volumen [%] > 97 > 97 > 97 > 97
Wellenhöhe 19 20 20 23
Anmerkung KFP/KGP/KVP/KBP = Füllkörper aus PP
KFC/KGC/KVC/KBC = Füllkörper aus PVC
2H PLASdek® Counter-Flow Cooling Tower Fills FC20.30 FC70.34
Contact surface [m²/m³] 110 94
Void ratio [%] > 95 > 93
Corrugation height 30 34
Note Our splash cooling fills are made of PP
2H PLASdek® Counter-Flow Cooling Tower Fills NET25 150
Contact surface [m²/m³] up to 130
Void ratio [%] > 97
Corrugation height 20
Note Our trickle grid fills are made of PP

We offer innovative components and solutions for sustainable processes in heat exchange, water and wastewater treatment and mass transfer applications with respect for the environment. Our professional team works to increase productivity and cost effectiveness in your unique application. If you need a tailor made solution ... We are available for you!