PLASdek® Counter-Flow Cooling Tower Fills

Different types for all requirements – available in PVC and PP

From small cooling towers to large cell and natural draught cooling towers: Our PLASdek® packings fulfill all requirements. Different types of film fills with large specific surface are highly suited for clean and medium water qualities, whereas for special operation conditions and for strongly polluted water grid structures are the best choice. Ask our experts. They have long time experience and will be grateful to help you choose the right fill for your application.

Features

  • Excellent heat and mass transfer

    • Due to high mixing turbulence by cross-fluted structure
  • High resistance to erosion

    • Provided by double folded PVC edges or reinforced PP edges
  • Self supporting structure

    • High bearing capacity achieved by large number of connecting points and variable sheet thicknesses
  • Flexibility in material and dimensions

    • Adaptation to plant requirements according to customer request
  • Long service life

    • Due to chemical, bacterial and UV resistance of PP and PVC

Overview: PLASdek® Cooling Fills made of Polypropylene

Highly efficient with large specific surface, suited for clean cooling water

KPP 312KZP 312KFP 319
Contact surface [m²/m³]232240150
Corrugation height [mm]121219
ChannelsCross-flutedCross-flutedCross-fluted

Low fouling fills, for slightly and medium polluted water

KVP 319KGP 320KBP 320KVP 323KFP 327
Contact surface [m²/m³]144142142125125
Corrugation height [mm]1920202327
ChannelsVertical flowVertical flow / off setVertical flow / off setVertical flowCross-fluted

Easy to clean, for special operation conditions, for strongly polluted water

NET25 150FC20.30KFP 638FC70.34
Contact surface [m²/m³]up to 1301107094
Corrugation height [mm]20303834
ChannelsGrid / diagonalCross-flutedCross-flutedGrid / horizontal
2H PLASdek® Counter-Flow Cooling Tower Fills
2H PLASdek® Counter-Flow Cooling Tower Fills
2H PLASdek® Counter-Flow Cooling Tower Fills
2H PLASdek® Counter-Flow Cooling Tower Fills

OVERVIEW: PLASDEK® COOLING FILLS MADE OF PVC

Highly efficient with large specific surface, suited for clean cooling water

KZC 312KPC 312KFC 319
Contact surface [m²/m³]240232150
Corrugation height [mm]121219
ChannelsCross-flutedCross-flutedCross-fluted

Low fouling fills, for slightly and medium polluted water

KVC 319KGC 320KBC 320KFC 327
Contact surface [m²/m³]144142142125
Corrugation height [mm]19202027
ChannelsVertical flowVertical flowVertical flow / off setCross-fluted

General Technical Data of 2H PLASdek® Fills

PPPVC
Void ratio [%]> 97
Length max [mm]2400
Width max [mm]600
Standard height [mm]300 or 600
Continuous operation temperature [°C]8055
Max. operation temperature (short term) [°C]9060
Maximum application temperature:

The operational temperature should be measured at the inlet pipe of the system and should not exceed the maximum temperature stated above.

High temperature applications:

Fill media in high temperature in PP (up to 100°C) available on request.

Flammability:

Products in flame retardant version according to American (ASTM E84, UL 94) and European standards (DIN 4102, NF P 92-501) are available on request. National regulations on fire protection should be taken into consideration before choosing a product.

DIFFERENT TYPES OF FILLS

2H PLASdek® Counter-Flow Cooling Tower FillsKPP 312 KPC 312KZP 312 KZC 312KFP 319 KFC 319KFP 327 KFC 327KFP 638 KFC 638
Contact surface [m²/m³]23224015012570
Void ratio [%]> 97> 97> 97> 97> 97
Corrugation height1212192738
NoteKFP/KGP/KVP/KBP = Fills in PP
KFC/KGC/KVC/KBC = Fills in PVC
2H PLASdek® Counter-Flow Cooling Tower FillsKVP 319 KVC 319KGP 320 KGC 320KBP 320 KBC 320KVP 323 KVC 323
Kontaktoberfläche [m²/m³]144142142125
Freies Volumen [%]> 97> 97> 97> 97
Wellenhöhe19202023
AnmerkungKFP/KGP/KVP/KBP = Füllkörper aus PP
KFC/KGC/KVC/KBC = Füllkörper aus PVC
2H PLASdek® Counter-Flow Cooling Tower FillsFC20.30FC70.34
Contact surface [m²/m³]11094
Void ratio [%]> 95> 93
Corrugation height3034
NoteOur splash cooling fills are made of PP
2H PLASdek® Counter-Flow Cooling Tower FillsNET25 150
Contact surface [m²/m³]up to 130
Void ratio [%]> 97
Corrugation height20
NoteOur trickle grid fills are made of PP

We offer innovative components and solutions for sustainable processes in heat exchange, water and wastewater treatment and mass transfer applications with respect for the environment. Our professional team works to increase productivity and cost effectiveness in your unique application. If you need a tailor made solution ... We are available for you!